BT Redcare Secure Issue 16 June 2010
Installation Manual Page 26 of 40 All rights reserved
Apply an alarm / restore condition to all used input pins.
These events will be signalled immediately over GPRS path if available.
Time
hh:mm:ss
Path
Indicator
Pin
CID
(zone)
SIA
(zone)
Description
10:07:00
0x13 or
0x23
4;3
R323
(904)
UR
(904)
Pin 4 Close (panel set)
10:08:00
0x13 or
0x23
2;1
E323
(902)
UA
(902)
Pin 2 panic alarm event
10:09:00
0x13 or
0x23
3;1
E323
(903)
UA
(903)
Pin 3 intruder alarm event
10:09:30
0x13 or
0x23
7;1
E323
(907)
UA
(907)
Pin 7 confirmed intruder alarm event
10:10:00
0x13 or
0x23
4;1
E323
(904)
UA
(904)
Pin 4 Open (panel unset)
10:10:02
0x13 or
0x23
2;3
R323
(902)
UR
(902)
Pin 2 panic alarm restore
10:10:03
0x13 or
0x23
3;3
R323
(903)
UR
(903)
Pin 3 intruder alarm restore
10:10:04
0x13 or
0x23
7;3
R323
(907)
UR
(907)
Pin 7 confirmed intruder alarm restore
10:15:00
0x13 or
0x23
12;1
E323
(912)
BA
(912)
Pin 12 Tamper alarm
10:15:10
0x13 or
0x23
12;3
R323
(912)
BR
(912)
Pin 12 Tamper alarm restore
Figure 18 - Typical ARC alarm log for Redcare Secure unit test pin alarms during
commissioning
Check with the ARC that these alarms have been received over the relevant paths.
Remote trigger of dual path test
The ARC can send the telemetry command ID=01, Data=00 to cause the Redcare Secure unit to
send a BSIA test message on all available paths. Within 70 seconds a pin 988 Event / Restore
will be received via each path.