BT Redcare Secure Issue 16 June 2010
Installation Manual Page 36 of 40 All rights reserved
Continued.
RPS function Active Low (Alarm sent on GPIP4 sets output Low, Alarm
acknowledged sets output High)
RPS function (Alarm sent on GPIP4 sets output High, Alarm
acknowledged sets output Low) – Default
Line voltage test. State of line voltage is indicated on LED‟s SS1 & SS2
Disable PSTN voltage monitoring
Enable PSTN voltage monitoring - Default
Use *0 for a pause, *1 for a star, and *2 for a hash.
Example *50*9*01470# will dial a 9 followed by a pause and then 1470
to ensure CLI is used
* 20 * TAID # Check
Digit
Set the TA (Account) number. (Optional) - Example * 20 * 4191000 # 1
Set the panel callback number (for panel remote access) to X. Default 7
Set the panel callback maximum time. Default 30 minutes
Set a static IP address X.X.X.X and subnet mask M.M.M.M
Eg. *10* 192 * 168 * 1 * 10 # 255 * 255 * 255 * 0 #
Set the Gateway address G.G.G.G
Eg *11* 192 * 168 * 1 * 1 #
Switch back to DHCP mode. Default
Select GPRS + Dialup PSTN mode. Default