BT Redcare Secure Issue 16 June 2010
Installation Manual Page 27 of 40 All rights reserved
Dial Capture test
If the alarm panel is connected to the Dial Capture port of the unit, generate panel test alarms /
restores and confirm that they are received at ARC.
Time
hh:mm:ss
Path
Indicator
CID
(zone)
SIA
(zone)
Description
10:20:00
0x13 or
0x23
R401
(001)
CL
(001)
Panel Close (panel set)
10:21:00
0x13 or
0x23
E120
(001)
HA
(001)
Panic alarm event
10:22:00
0x13 or
0x23
E130
(002)
BA
(002)
Intruder alarm event
10:22:30
0x13 or
0x23
E139
(001)
BV
(001)
Confirmed intruder alarm event
10:23:00
0x13 or
0x23
E401
(001)
OP
(001)
Panel Open (panel unset)
10:23:02
0x13 or
0x23
R305
(000)
OR
(000)
System Reset (panel reset)
Figure 18 - Typical ARC alarm log for Redcare Secure dial capture alarms during
commissioning
Actual alarms will be dependant on panel type and protocol.
If the ARC receives a Bad Panel Checksum Error, the panel is not transmitting in a
format known to the BT Redcare Secure unit
If the ARC receives a Panel Type Mismatch Error, the BT Redcare unit is not
configured for the correct panel format.
Communication fault testing
Disconnect the wireline path connection and confirm that the correct alarm is received at the ARC
Secure 2 & 3
Pin 955 after 120 seconds, Restore after 30 seconds
Secure IP
Pin 1023 after <60 seconds, restore after < 60 seconds
Notes
A PSTN voltage fail alarm (955) will be generated by the unit, and generally signalled over
the GPRS path, if the PSTN voltage stays below 1.5V for 120s. A restore will be signalled
after 30s of the PSTN voltage returning to normal. (Default settings)
The transmission path of messages can be identified at the ARC by looking at the
receiver number, generally within the raw message data. (13 = Wireline, 23 = GPRS).
As a general rule, messages signalled on zones >900 are Redcare Secure unit generated
events, whereas messages signalled on zones <900 are panel generated events.